  df-52202 ? 07/13/04 ? page 1 of 3 general the fire?lite FCPS-2404 is a compact, cost-effective, nac power expander. its filtered 24 vdc output can provide up to 4.0 amps of current to drive one style y (class b) nac (notification appliance circuit). the facp's (fire alarm control panel) nac is connected to the power expander's input circuit. when the control input circuit activates due to reverse polarity of the facp's nac, the power expander will activate its nac circuit. the FCPS-2404 is compatible with 12 vdc and 24 vdc control panels. features  4 amps total of continuous current available.  one 24 vdc style y (class b) nac.  one optically-isolated input/control circuit, compatible with 12 vdc and 24 vdc control panel.  external strobe synchronization could be added with ul listed synch module, which can be housed in the fcps- 2404.  can be wired daisy-chain style.  self-contained in compact, lockable cabinet (15" [381 mm] h x 14.5" [368 mm] w x 3.050" [775 mm] d).  output is filtered and completely power limited.  integrated supervised battery charger for lead acid or gel type batteries.  uses only 7 ah (amp hour) batteries ? can be accomodated in the power supply cabinet.  nac supervised by host facp.  earth fault detection by host facp.  fixed terminal blocks for field wiring capable of accepting 12 ? 22 awg wire.  ac fail form-c relay contacts (fail-safe).  battery/charger trouble form-c relay contacts (fail safe).  optional hardware kit #90273 to be used when installing addressable or synchronization modules. led indicators  ac power on (green) led.  battery/charger trouble (yellow) led. specifications primary (ac) power ? tb1  120 vac 50/60 hz, 1.45 amps maximum.  wire size: minimum #14 awg (2 mm2) with 600v insula- tion. control input circuit ? tb3, terminals 1 (+) & 2 (?) alarm polarity  trigger input voltage: 9 to 32 vdc.  input current draw in alarm polarity: 16 - 32 volts, 10 ma maximum. 9 -16 volts, 4 ma maximum. important: do not use shielded wire for control input circuit. nac output circuit ? tb3, terminals 3 (+) & 4 (?) alarm polarity  voltage rating: 24 vdc.  current: 4 amps maximum total continuous current.  style y (class b) ? requires end-of-line resistor from circuit connected to input.  refer to fire?lite device compatibility document for listed compatible devices. important: do not use shielded wire for nac output circuit. ac fail relay contact rating ? tb6  fail-safe relay (normally energized, transfers with loss of power).  1 amp @ 30 vdc. FCPS-2404 s2424 FCPS-2404 24 volt, 4 amp nac power expander df-52202  d-110 july 13, 2004 section: power supplies/accessories www.firelite.com mea 141-01-e 7315-0075:197 california state fire marshal firelite? alarms is a honeywell company. this document is not intended to be used for installation purposes. we try to keep our product informa- tion up-to-date and accurate. we cannot cover all specific applications or anticipate all requirements. all specifications are subject to change without notice. for more information, contact firelite alarms , one fire-lite place, northford, connecticut 06472. phone: (800) 627-3473, toll-free fax: (877) 699-4105.
page 2 of 3 ? df-52202  07/13/04 battery/chargertrouble contact rating ? tb5  fail-safe relay (normally energized, transfers with loss of power).  1 amp @ 30 vdc. secondary power (battery) charging circuit  supports lead acid and gel type batteries only.  float charge voltage: 27.6 vdc.  maximum charge current: 750 ma.  maximum battery capacity: use only 7.0 ah batteries.  FCPS-2404 draws maximum standby current of 40 ma from batteries (includes end-of-line relay currrent if in- stalled). auxiliary power connector ? p3  used for powering modules inside cabinet, such as control modules.  voltage rating: 24 vdc.  current: 30 ma maximum. FCPS-2404 board layout p3 internal 24 vdc power (nonsupervised) ac fail report jumper ac fail relays contacts battery/charger trouble relay contacts nac output - supervised (alarm polarity shown) nac input from facp - supervised (alarm polarity shown) note: no t-tapping addtional notification appliances important : do not use shielded wire for control input or nac output circtuits p2 battery connector (supervised) tb1 ac power connector (supervised) f2 fuse - 8 amp for battery f1 fuse - 1 amp for charger 2404bord.wmf
df-52202  07/13/04 ? page 3 of 3 product line information FCPS-2404 nac power expander (120 vac). includes main printed circuit board, transformers, red enclosure, and installation instructions. cmf-300 intelligent addressable control module. mdl sync module for use with spectralert series, red . mdlw sync module for use with spectralert series, white . bat-1270 battery, 12 volt, 7.0 ah (two required) . 90273 hardware kit to be used when installing addressable or synch modules. fcps-24rb replacement motherboard. control module or sync module control module mounting (if sync module used above) or second control module - + 24 vdc FCPS-2404 24 vdc - - + + slc out to next addressable device slc in from facp or previous addressable device 2404app.wmf controlling FCPS-2404 with control module and internal power polarized bell strobe horn


▲Up To Search▲   

 
Price & Availability of FCPS-2404

All Rights Reserved © IC-ON-LINE 2003 - 2022  

[Add Bookmark] [Contact Us] [Link exchange] [Privacy policy]
Mirror Sites :  [www.datasheet.hk]   [www.maxim4u.com]  [www.ic-on-line.cn] [www.ic-on-line.com] [www.ic-on-line.net] [www.alldatasheet.com.cn] [www.gdcy.com]  [www.gdcy.net]


 . . . . .
  We use cookies to deliver the best possible web experience and assist with our advertising efforts. By continuing to use this site, you consent to the use of cookies. For more information on cookies, please take a look at our Privacy Policy. X